This algorithm analyzes trend data and returns a true result, indicating that an exception existed, if the building was occupied,
the supply fan command was on, the supply fan status was on, the heating valve position or the heating valve command was greater
than 0%, and the cooling valve position or cooling valve command was greater than 0% for 15 minutes. A false result indicates
that nothing was wrong.
Input ORDs
slot:/Algorithm/English/Simultaneous_Heat_Coolslot:/Algorithm/Metric/Simultaneous_Heat_Cool
Wire sheet
Figure 41. Fragment of the Simultaneous Heat Cool algorithm wire sheet