This algorithm evaluates static pressure trend data. It produces a true result, indicating that an exception existed, if a
building was occupied, an AHU unit’s supply fan was on, the supply fan status indicated that the fan was on, the supply air
static pressure was less than 90% of the supply air static pressure stepoint, and all these conditions existed for 30 minutes.
A false result indicates that nothing was wrong.
ORDs
slot:/Algorithm/English/Low_Supply_Static_Pressureslot:/Algorithm/Metric/Low_Supply_Static_Pressure
Wire sheet
Figure 26. Low Supply Static Pressure algorithm