This algorithm evaluates static pressure trend data. It produces a true result, indicating that an exception existed, if a
building was occupied, an AHU unit’s supply fan was on, the supply fan status indicated that the fan was on, the supply air
static pressure was greater than 110% of the supply air static pressure stepoint, and all these conditions existed for 30
minutes. A false result indicates that nothing was wrong.
ORDs
slot:/Algorithm/English/High_Supply_Static_Pressureslot:/Algorithm/Metric/High_Supply_Static_Pressure
Wire sheet
Figure 20. High Supply Static Pressure