PumpExceedingSetpoint

This algorithm uses three inputs to determine if the pressure in a secondary chilled water pump exceeds the expected setpoint.

The conditions that must be met for this algorithm to return a value of true are:

  • Secondary chilled water pump command is on.
  • Secondary chilled water pump is on.
  • Secondary loop differential pressure is above 110% the setpoint for more than 30 minutes.

Input ORD

slot:/Algorithm/English/PumpExceedingSetpoint

slot:/Algorithm/Metric/PumpExceedingSetpoint

Wire sheet view

Figure 31.   Pump pressure above setpoint wire sheet
Image