High_Outside_Air_Intake

This algorithm evaluates trend data collected from an AHU unit. It returns a true result if four conditions are met for an hour. Otherwise it returns false. The four conditions are: system was occupied, the command had been given to turn the supply fan on, the supply fan was on, and the outside air flow coming in was more than 100% of the outside airflow setpoint. A false result indicates that air coming in from the outside was normal.

Ords

slot:/Algorithm/English/High_Outside_Air_Intake

slot:/Algorithm/Metric/High_Outside_Air_Intake

Algorithm

Figure 19.   High Outside Air Intake algorithm
Image