Cooling_Valve_Open_100_Percent

This algorithm evaluates trend data. It produces a true or false result for historical data, if a building was occupied, the supply fan was on, the supply fan status indicated that the fan was on, and the cooling valve was wide open (100% open) for 30 minutes. A true result indicates that an exception existed; a false result that nothing was wrong.

ORDs

slot:/Algorithm/English/Cooling_Valve_Open_100_Percent

slot:/Algorithm/Metric/Cooling_Valve_Open_100_Percent

Wire sheet

Figure 8.   Cooling Valve Open 100% algorithm
Image