dataRecovery license, and the platDataRecoverymodule. The other JACEs require
dataRecovery license, and the platDataRecovery module. The module works with the SRAM buffer to continuously save changes as “deltas”. Essentially, this feature automatically
“records” all changes during runtime, for “playback” upon station startup after a power outage.Providing that the JACE is properly licensed, no other configuration is required for this combination to provide SRAM support. This feature automatically works for the JACE-8000, JACE-6E, or JACE-3E, as well as for other platforms with the SRAM option card (providing the platDataRecovery software module is installed).
An interface “window” is automatically provided in the station running on the JACE, via the dynamically created “DataRecoveryService” under its PlatformServices container. A special view on this platform service allows verification of operation, and if ever necessary, a means of troubleshooting.