ccn-CcnFidTable

This table configures data for FID-type proxy points.

Image

To access these properties, expand Config > Drivers > CcnNetwork > CcnDevice, double-click CcnTableGroup and double-click a CcnFidTable.

Property Value Description
Debug On true or false default Turns debugging on (true) and off (false).
Table Type number Configures the type of table. For FID tables, valid type is 501H.
Table Type String text Describes the table.
Table Instance number Assigns a table number to the table.
Table Num number Assigns a unique table number within Table Instance.
Table Name text Assigns an eight-character name to the table. This is the only property that goes to field device.

To change the name in the device after entering it here, invoke the Fetch action on the table.

An invalid table name is treated as “T.” The driver sends the first eight characters of the name to the field device.

 NOTE: Change the Table Name property on the Property Sheet only. Avoid renaming the table name on the wire sheet, slot sheet etc. 

This operation is controller specific.

Table Block Count number Configures the table’s block count (generally 10-15).
Learn Status read-only Reports the status of the network-level learn command (busy, idle or error).
Poll Frequency drop-down list Selects one of three pre-configured polling frequencies: Slow, Normal, Fast.
Point Learn Count number Reports the number of points found during the latest discovery job.
Point Create Count number Reports the number of points created during the latest create process.
Setpoint Type number Reports the type of setpoint.

Actions

  • Fetch retrieves additional table-related information.