ccn-CcnDataTable

This table configures a table with data-type proxy points.
Figure 5.   Ccn Data Table properties
Image

To access these properties, expand Config > Drivers > CcnNetwork > CcnDevice > CcnPocTable, double-click CcnPocTable and double-click a CcnDataTable.

Property Value Description
Debug On true or false default Turns debugging on (true) and off (false).
Table Type number Configures the type of table. For Data tables, valid type is >127.
Table Type String text Describes the table.
Table Instance number Assigns a table number to the table.
Table Num number Assigns a unique table number within Table Instance.
Table Name text Assigns an eight-character name to the table. This is the only property that goes to field device.

To change the name in the device after entering it here, invoke the Fetch action on the table.

An invalid table name is treated as “T.” The driver sends the first eight characters of the name to the field device.

 NOTE: Change the Table Name property on the Property Sheet only. Avoid renaming the table name on the wire sheet, slot sheet etc. 

This operation is controller specific.

Table Block Count number Configures the table’s block count (generally 10-15).
Learn Status read-only Reports the status of the network-level learn command (busy, idle or error).
Poll Frequency drop-down list Selects one of three pre-configured polling frequencies: Slow, Normal, Fast.
Poc Table Type read-only Displays the type of Poc table.
Data Block number Identifies the data block.
Point Create Count number Reports the number of points created during the latest create process.
Point Force Refresh true or false default Turns this function on (true) and off (false).

Actions

  • Fetch retrieves additional table-related information.