kitcontrol-InterstartDelayMaster

This component defines the master in an inter-start delay sequence. Use it in conjunction with one or more InterstartDelayControl objects.

InterstartDelayMaster is available in the HVAC folder of the kitControl palette.

An available action for this component is DelayTimerExpired.

Figure 1. InterstartDelayMaster properties


PropertyValueDescription
Slave LinkORDLinks to the slave InterstartDelayControl components.
Default Delayhours minutes seconds (defaults to zero)Defines the how long to wait before starting a request. The component uses this value only if Delay Time is not defined.
Active Delayread-only true or false (default)Displays if the delay is active.

true indicates that the interstart delay is active

false indicates that the interstart delay is not active.

Delay Timeread-only hours minutes seconds (defaults to zero)Displays the length of the current delay.
Delay Start Timeread-only clock timeDisplays the time that the current delay started.
Num Objects Waitingread-only number (defaults to zero (0))Displays the number of objects currently waiting to start.