Provisioning requires a connection to each remote platform/station.
For each NiagaraStation in the client station’s NiagaraNetwork, you must confirm the port and enter the
corresponding platform daemon credentials of its host. The simplest
way to do this is by using either the Station Manager or Provisioning Manager views.
All platform/stations to be provisioned are running. Each
has its own signed server certificate recognized by the client station
for server authentication.
- In the Nav tree, expand , right-click NiagaraNetwork and select .
The
Provisioning Manager opens.

Each row in the table represents a connection to a remote
server platform/station.
- Select one or more (a group) of stations and click Edit.
The system opens an
Edit window.

- Enter platform connection credentials, and, if using a
non-default port address, change the port from the default port 5011
to the port number used and click OK.
These platform credentials and port should be the same credentials
and port you use when you open a platform connection directly to each
remote host.
Upon the next monitor ping of the host’s platform
daemon, its Station Run State should change from Unknown to Running and
the station’s Platform Connection extension
should now have a status of ok.
- To confirm the platform connection immediately, right-click
the station’s Platform Connection extension
and click .
- Confirm that the station, as shown in the Provisioning
Manager, has a platform status of ok.
- To test the validity of the credentials, right-click the
station row and click .
Repeat this procedure for each NiagaraStation listed in the Station Manager.