Provisioning considerations when JACE controllers remain

Sometimes one or more JACE controllers may need to remain running AX-3.8, yet continue to be in the migrated Supervisor’s NiagaraNetwork. This is supported by the N4.0 Supervisor, including many provisioning operations. For example, the backup of AX-3.8 stations and installation of AX-3.8 software.

For proper support, you should import the software database of the former AX-3.8 Supervisor into the software database of the N4.0 Supervisor. This copies over all the versioned NiagaraAX software modules and .dist files to the new Supervisor, and makes them available for provisioning of the older platforms.

To do this when the N4.0 Supervisor is installed on the same PC as the former AX-3.8 Supervisor:

  1. Use Workbench to open a platform connection to the N4.0 Supervisor, then access the Software Manager view.
  2. Click the Import button at the bottom, and then Import software from directory.

    Image

  3. As shown above, in the Directory Chooser popup, navigate to the AX-3.8 Supervisor’s installation folder, then expand to find its sw subfolder. Select it and click Choose.

    Image

    Progress is displayed in a popup dialog similar to the one above, while software files are analyzed for versions and then copied into appropriate subfolders in the N4.0 Supervisor’s software database. When finished copying, the normal Software Manager view opens.

If the former AX-3.8 Supervisor is on a different PC than the N4.0 Supervisor, you perform the same procedure. However, first copy the entire software database (!\sw folder) from the AX-3.8 Supervisor to a location accessible from the N4.0 Supervisor, such as on a USB flash drive, etc. Then navigate to that location from the Software Manager while platform-connected to the N4.0 Supervisor.