When creating points, I get the message: Read fault: illegal data address.
Check the address in the point against the documented address for the data item.
The NumericPoint or NumericWritable I’m creating for a float or long (2-register) value reports a value of zero (0) or an
impossibly large value instead of the expected value, yet the point still reports a status of {ok}.
Verify that the correct byte order settings exist for float and long values in the parent device.