Default container.
If you expanded the property sheet, you see the four range properties: Enabled, Critical Data, Starting Address Offset, and Size.
If you used the action, the Add Range window opens.

By default, a slave device copied from the modbusSlave or modbusTcp palette has the same values for each of the four default register range containers: Enabled, Starting Address Offset: 1, Size: 64.
If a holding register range is set to a starting address of 250 with a size of 75, the driver assigns an effective Modbus address range of 40250 to 40325.