Initiating a controller shutdown

When locally servicing an installed and configured (commissioned) unit, use this feature before removing power.
Prerequisites: The controller has been commissioned ( Niagara 4 installed, platform configured, a station installed) and the unit is running the station. The BEAT LED is flashing at the normal 50%/50% On/Off duty cycle rate.
Perform the following steps:
  1. Press and hold the recessed SHUT DOWN button just until the Green SHUT DOWN LED illuminates.
  2. Release the SHUT DOWN button.
    The station and software is put into a safe state. The shutdown process starts. During shutdown, the SHUT DOWN LED blinks in working mode.

    When shutdown is done, the SHUT DOWN LED turns off.

  3. You can safely remove the 24V power from the unit.
    If the system cannot be put into a safe state, the SHUT DOWN LED blinks in error mode: two quick 200ms flashes On, 3 seconds off, repeating.