You may need to install a copy of a station created on another platform. In such cases, the station bog file
passphrase most likely differ from that of the target platform, and
many times the passphrase and user credentials are unknown. In that
event, before you can run the station, you must edit the bog file offline.
This procedure describes the steps to edit the bog file offline, set
a new passphrase, change the admin user password, and install the
copied station on the target platform. This procedure works for a Supervisor or controller station, and assumes the copied
station is provided as a ZIP file.
The source and target controllers are running the latest Niagara version.
You are using Workbench running on a PC.
You have a NiagaraStation copy that
was created on another platform and the BOG file passphrase is not
known.
Note: The copied station might be a single *.bog file but
typically it is provided as a ZIP file containing a collection of
files that may include any combination of the following: components
(*.bog), templates (*.ntpl), Px files (*.px), graphic images, and
etc.
- Using Windows File Explorer, extract the downloaded ZIP
file and copy the station folder to your User Home stations folder
for your installation, (C:\Users\UserName\Niagara4.x\brand\stations).
- In the Workbench NavTree, expand and navigate to the
station folder just copied to that location.
- Expand the station folder and double-click config.bog to open the file.
- On the Workbench tool bar, click
(Bog File Protection tool).The
Bog File Protection tool allows you
to enter, change, or add a bog file passphrase.
CAUTION: Any password values that are encoded with the current passphrase
will be cleared. So you will need to enter/re-enter the passwords
that the station uses as a client, such as the passwords configured
on a station-to-station connection or the Email Service.
- In the Bog File Passphrase window,
click Force the file to start using a different passphrase
that you specify, enter the new Passphase and Passphrase
Confirm values and click Update and on the
subsequent view, click Close.
- In the NavTree, expand , and double-click UserService.
- In the AX User Manager, double-click
the admin user and under Authenticator, change the Password and Password
Confirm values.
Repeat this step as needed to change passwords for other users.
- Right-click the config.bog file and
click Save.
- Open the Station Copier and copy the
station from the your User Home to the target platform.
On completion, you have successfully edited the station config.bog offline, set a new passphrase, and changed
the admin user password. Typically, the station will autostart after copying. If
not, use Application Director to start it. At
this point you can connect to the station.