Mbus Proxy Ext

This extension, which configures point properties is located beneath any Mbus proxied point.

This extension is visible once you add a point to the point database.

Image
Property Value Description
Status read-only Indicates the condition of the component at the last check.

{ok} indicates that the component is licensed and polling successfully.

{down} indicates that the last check was unsuccessful, perhaps because of an incorrect property, or possibly loss of network connection.

{disabled} indicates that the Enable property is set to false.

{fault} indicates another problem. Refer to Fault Cause for more information.

Fault Cause read-only Indicates the reason why a system object (network, device, component, extension, etc.) is in fault. This property is empty unless a fault exists.
Enabled true or false Activates and deactivates use of the component.
Conversion Drop-down list Defines how the system converts proxy extension units to parent point units.

Default automatically converts similar units (such as Fahrenheit to Celsius) within the proxy point.

 
NOTE: In most cases, the standard Default conversion is best.
 

Linear applies to voltage input, resistive input and voltage output writable points. Works with linear-acting devices. You use the Scale and Offset properties to convert the output value to a unit other than that defined by device facets.

Reverse Polarity applies only to Boolean input and relay output writable points. Reverses the logic of the hardware binary input or output.

500 Ohm Shunt applies to voltage input points only. It reads a 4-to-20mA sensor, where the Ui input requires a 500 ohm resistor wired across (shunting) the input terminals.

Tabular Thermistor applies to only a Thermistor input point and involves a custom resistance-to-temperature value response curve for Type 3 Thermistor temperature sensors.

Tuning Policy Name   Selects the tuning policy for this point.
Read Value read-only Displays the actual value imported from the device, and formatted based on device facets. The display accords with the point facets.
Mbus Unit text Displays the unit as defined in the Mbus specification. The unit is text only and can be changed for information purposes.
Description text Describes the point. This text can be changed.
Orthogonal Description text Displays the Orthogonal Description as defined in the Mbus specification. This can be changed.
Number Type read-only Reports the type of number for the input.
Message Slot Number read-only Refer to the manufacturer's documentation.
Record Number read-only Refer to the manufacturer's documentation.
Function read-only Refer to the manufacturer's documentation.
Exponent read-only Reports value information provided by the device manufacturer.
Manu Spec Def Element Ord read-only Refer to the manufacturer's documentation.
Device Mode read-only Refer to the manufacturer's documentation.
Out read-only Reports the current value and status of the point.