Getting started

A Meter Bus (Mbus) network consists of one master device and one or more slave devices (up to 250 devices) interconnected using twin wire cabling. The master device controls the communications over the whole network. This Mbus driver conforms to the European standard: EN13757. Getting started involves setting up the driver components, configuring communication properties (baud rate, etc.), and configuring timing properties.

In a network with a JACE controller, the JACE is connected directly to the master device via an RS232 cable. The JACE takes on the control functions of the master device, interrogating the network for information.

While all slave devices must be compatible with a communication rate of 300 baud, this driver supports multiple baud rates, which means that all slave devices, sharing the same network, can communicate with the master at the most efficient baud rate for the device.