Ip Address in the properties as required for the unit.
Refer to the manual.
Use the built-in Web Server to obtain a set of example readings from the meter, for use in establishing what the manufacturer’s properties represent.
This meter uses manufacturer-specific data, a primary address of zero (0) and the FC bit toggle. A double discovery is required.
For a double discovery, first carry out a discovery, then add the device (do not discover the history or points), set up device properties (see following), remove the device from the network database (a device action), and carry out another discovery. This ensures that the Fc Bit is in the correct state and in agreement with the meter. Now discover the history or points.
Device properties should include: Device Cycle Quantity = 1, Reset Required = true and Fc Bit In Use = true.
After reading the data, examine it and set up the scaling factor to give the correct readings. The scaling factor is defined
by the Conversion property in the proxy extension of each point. For example, you might choose a Conversion of Linear with Scale and Offset instead of the default settings.