Before discovering devices, this procedure configures general network properties.
Prerequisites: The JACEcontroller is installed, your computer is connected to the network and running
Workbench.
Perform the following steps:
- Right-click the MbusSerialNetwork component in the Nav tree, and click .
The
Property Sheet opens.
- Configure properties based on the meters you are about to discover.
Consider setting:
Retry Count to zero (0). This is because of some of the testing mechanisms required for changing slave parameters.
Response Timeout to 12.5 seconds.
Inter Message Delay to 12.0 seconds.
- Expand the
Serial Port Config property and enter the Port Name.
- Set up serial port properties.
The defaults are: none, 300, 8, 1, Even.