Node Switch (bacnet-NodeSwitch)

This component manages the initiated and accepted direct connections made with other SC nodes.
Figure 49.   Node Switch properties
Image

To access these properties, expand Config > Drivers > BacnetNetwork > Bacnet Comm > Network > ScPort and double-click Node Switch.

In addition to the standard properties (Status and Fault Cause), these sets of properties configure a node switch.

Property Value Description
Accept Enabled true or false (default) Determines if this port can accept direct connections from other nodes (true) or not (false). To support accepting connections, a BACnet/SC user must be associated with this port.
Initiate Enabled true or false (default) Determines whether (true) or not (false) this port is enabled to initiate direct connections to other nodes.
Web Socket Acceptor additional properties Configure the web socket servlet used to accept direct connections from other SC nodes. For property descriptions, refer to “Node Switch/Hub Function, Web Socket Acceptor (bacnet-JettyScWebSocketAcceptor).”
Accept Uris array
Identifies the possible URIs that an initiating SC node can use to make a direct connection to this node. The values in this property are sent in the address resolution ack message.
Connections additional properties Configure node switch connections. For these properties, refer to “Connections (bacnet-NodeSwitchConnections).”

Actions

  • Add Sc User adds a secure connect user to the UserService. If a user is already associated with BACnet/SC, you receive an error message. No message confirms the addition.
  • Remove Sc User removes a secure connect user from the UserService. No message confirms the deletion.