Link, Hub Connector (bacnet-HubConnector)

This component configures a primary hub and, optionally, a failover hub. The same component is present in an ScPort and ScHubPort.
Figure 54.   Hub Connector properties
Image

To access these properties, expand BacnetNetwork > Bacnet Comm > Network, then expand either ScPort or ScHubPort, expand Link and double-click Hub Connector.

In addition to the standard properties (Status and Health), these properties configure the hub connector.

Property Value Description
State read-only Indicates the current high-level state of the hub connector.
Sub State read-only Indicates the current more detailed state of the hub connector.
Primary Connection additional properties Configures the connection to the primary hub. For a description of these properties, refer to “Hub Connector connection (bacnet-HubInitiatingConnection).”
Failover Connection additional properties Configures the connection to the optional failover hub. For a description of these properties, refer to “Hub Connector connection (bacnet-HubInitiatingConnection).”

Actions

  • Force Connect causes an immediate re-connection attempt to the primary hub when the hub connector is not connected to any hub or is connected to the failover hub. An error will be displayed if the hub connector is not in one of these sub states.
  • Disconnect causes the active hub connection to be disconnected. This may result in a re-connection attempt to the primary hub.