To access this property expand, , double-click Prog
In addition to the common properties (Status and Fault Cause), this component has these properties.
| Property | Value | Description |
|---|---|---|
| Poll Frequency | drop-down list (defaults to Normal)
|
References the On Demand Poll Scheduler rates under the NiagaraNetwork’s History Policies container slot.
Configures how often this type of poll occurs. |
| Object Id | drop-down list and number (from 0 to 4194302) |
Identifies each device and component by the type of entity (
Object Id) combined with a unique Instance Number.
For devices (controllers, instruments, meters, etc.), |
| Object Name | text in the format name.name.name.name (default includes the entire component path in the station using period (“/) delimiters between parent.child levels) |
Identifies a BACnet object. This name should be unique within this specific device.
For components, this name includes the entire component path under the station’s Config using period (.) delimiters between parent.child levels. This enforces (externally) the BACnet requirement for unique names for all objects in a device. For a proxy point, this is the default name in the station. You can shorten or edit |
| Object Type | drop-down list of BACnet objects |
Reports the type of object.
|
| Program State | read-only | Reports the current state of the program. |
| Program Change | drop-down list | Selects a program transition. |
| Status Flags | read-only indicator and check boxes |
Configures four status flags for BACnet. These options are available to enable detection of specific status conditions.
|
| Out of Service | true (default) or false |
Affects only the BACnet exposure and access to the source component. If the source (exported) component is a proxy point,
the equivalent
Enabled property in its ProxyExt is not affected.
You can set this property to |