Service Enabled. The main use case for this property is for JACE-3E or NPM6E-based controller (JACE-6E, JACE-603, and JACE-645) with an installed backup battery, where you do not want it to use SRAM. This property setting is retained in any future controller upgrades.

By default, the Service Enabled property is true. This is appropriate if the controller has no backup battery installed—for example, the JACE-3E and JACE-6E ship from the factory without a battery.
false, providing:
Battery Present property in the station’s PlatformServices container is set to true.Shutdown Delay time to no higher than the default of one (1) minute.Service Enabled to false.
Service Enabled to false, the DataRecoveryService no longer records runtime database changes to SRAM. The controller depends entirely on its backup battery to preserve station data upon a power loss!