Poll Events Enabled = true) on the MaxproNVR component, the driver polls for events. You can configure the number of events the camera reads in each
poll. The driver reads the selected number of events per poll based on the last timestamp (also a property on the MaxproNVR
component). The driver updates the Last Read Timestamp with the timestamp of the last received event during the polling cycle.
This timestamp becomes the starting point form the next poll.
During event polling, when the driver receives a camera-motion-started event from the camera, it sets the Motion Detected point under the camera to true. When the camera receives a camera-motion-stopped event from the camera, it sets the Motion Detected point under the camera to false. The custom alarm extension, Maxpro Alarm Ext, automatically generates alarms for each camera-motion event received from
the Maxpro NVR. It creates an alarm record with the same timestamp as the event timestamp received from the NVR.