obixDriver-ObixExportManager

This view discovers, adds, and manages export descriptors (ObixExports) for control points in the local station, such that remote oBIX clients can participate in continuous control applications (meaning, link into specific prioritized inputs of specific points). It is the default view of the ObixExportFolder under the Obix Network.
 NOTE: In an Obix Network used only in a Niagara R2 station all interaction with oBIX devices is limited to Niagara R2 hosts. The ObixExportFolder and ObixExports are not used, as the Niagara R2 stations operate as oBIX servers only (they have no client interface). 
Figure 21.   Obix Export Manager view
Image

To view, double-click the Exports folder in the Nav tree, or right-click and select Views > Obix Export Manager.

Discovered pane

Although not a standard view in the driver architecture, it is similar to other manager views in that there is a Discovered pane (if in Learn mode) and a Database pane.

The Discovered pane in the Obix Export Manager view has these available columns:

Discovered pane columns

Column Description
Name Reports the name of the component in the local station.
Path Reports the station path of the component, relative to the root.
Type Identifies the type of component. Currently, only writable control points (including writable proxy points) can be added to the database: BooleanWritable, EnumWritable, NumericWritable, and StringWritable.

Database pane

By default, these columns appear in the Discovered pane of the Obix Export Manager view:

Database pane columns

Column Description
Name Reports the name of the export descriptor, often left the same as the source control point.
Point Reports the ORD for the slot in the station for this control point.
Value Reports the current out value for the control point.
Priority Identifies the Priority input of the control point exported (linked) to oBIX for remote writes.
Fault Reason
Explains why an export descriptor is in fault. Typically, this reflects an invalid configuration, such as selecting a Priority level that is already linked on the target control point.
Facets If configured, shows the facets in use by the target control point.