Installing software

This procedure covers installing the software on the supplicant device via commissioning.
Prerequisites:
  • The Supervisor installation ( Workbench) used to commission the JACE/Edge device is has the Niagara 4.8 (or later) release installed.
  • If you wish to have the station-level configuration view, the latest ieee8021X-*.jar files should be in the !modules folder for the release of Niagara you are using, where ! replaces the folder path.
 
NOTE: The Nav Container view for the platform is always available for the Niagara 4.8 Workbench. If the Workbench environment has the necessary modules, no additional modules need to be installed for the platform-level IEEE 802.1X Configuration view.
 

Perform the following steps:
  1. Connect the Supervisor and supplicant device to an open (not secure) network.
  2. Download from Niagara Central the latest Niagara 4.8 installer (or the module files: platIEEE8021X-rt.jar and platIEEE8021X-wb.jar, if the latest version of Niagara 4.8 is already installed).
  3. Run setup.exe or save the modules in the Niagara\version\modules folder, where version is the release version number of Niagara.
  4. Commission the supplicant device, installing platIEEE8021X-rt.jar during the software step.
     
    NOTE: If not done already, be sure to install the Niagara 4.8 ieee8021x license feature on the supplicant device.
     
  5. Once commissioning is complete and the device reboots, connect to the platform and continue the installation by setting up security, and configuring IEEE 802.1X properties (described in separate procedures following this one).
When you have configured the supplicant device, disconnect from the open port and connect it to an authenticated network segment. If you can access the supplicant device using the expected IP address, your configuration has worked. You may need to use a serial cable to diagnose problems.
 
NOTE: See the System Shell menu for added IEEE 802.1X options.