alarmOrion-OrionAlarmService

The alarmOrion provides a way to handle a large number of alarms (i.e more than 200,000). It requires Orion database system. The alarmOrionService supports the RDBMS platform. The rdb provides database ords used to configure exported data in the RDBMS database.

The OrionAlarmService component is available in the alarmOrion palette.

Figure 1. OrionAlarmService Properties


In addition to the standard properties (Status, Enabled, and Fault Cause), this component provides these properties.

To access, expand Config > Services and right-click OrionAlarmService > Views > AX Property Sheet.

TypeValueDescription
Alarm Db Config1–250,000 recordsDefines the number of alarm records to store in the histories database. When the capacity is reached, newer alarm records overwrite the oldest records.
Alarm Classdrop-down list (defaults to Medium)
Defines alarm routing options and priorities. Typical alarm classes include High, Medium and Low. An alarm class of Low might send an email message, while an alarm class of High might trigger a text message to the department manager.
Master Alarm Instructionsadditional propertiesClick the icon to open a window for adding and managing alarm instructions. Following are the instructions:

Add creates a new instruction.

Edit edits a existing instruction.

Remove deletes the selected instruction from the list.

Move Up/Down changes the order of the instructions in the list.

Coalesce Alarmstrue or false

When true is selected and saved, this property combines alarm notifications, which may improve system performance and lower network traffic. However, by combining alarm notifications, in some cases (when an alarm is initiated and quickly cleared), you may only see the “alarm cleared” notification and not the original alarm. To see all alarm notifications individually, select false. When false is selected and saved, the Coalesce Alarms does not combine the alarms, but sends individual alarm notifications.

Note: If sequences or notifications in the Supervisor station are triggered by alarms, you should not coalesce alarms. You do not coalesce alarms if you may need to document security incidents.
DatabaseordProvides the ord path to the database that is used by the Orion Alarm Service.
RdbAlarmDatabaseConversionadditional propertiesConfigures additional parameters to convert a RDBMS to an Orion database.