alarm-OutOfRangeAlarmExt

This extension implements a standard out-of-range alarming algorithm, and applies it to points with a status numeric output. This alarm extension is available in the Extensions folder of the alarm palette.

Algorithm properties

These properties are unique to the OutOfRangeAlarmExt.
PropertyValueDescription
Fault Algorithm, High Limittrue, falseEnables and disables high limits for the fault algorithm.
Low Limittrue, falseEnables and disables low limits.
DeadbandnumberDefines a band of input values where the output is zero.
High Limit Texttext stringDefines a bformat, which displays when a high limit is reached.
Low Limit Texttext stringDefines a bformat, which displays when low limit is reached.
Offnormal Algorithm, High Limittrue, falseEnables and disables high limits for the offnormal algorithms.
Limit Enableoption boxEnables the configuration of limits.