alarm-ConsoleRecipient

This component manages the transfer of alarms between the alarm history and the alarm console. The ConsoleRecipient is available in the alarm palette. For example, the console recipient gets unacknowledged alarms from the alarm history and updates the history when they are acknowledged. To view this property sheet, right-click the ConsoleRecpiient component in the Nav tree and click Views > Property Sheet.

The default view of the console recipient is the alarm console view.

Console recipient properties are displayed and edited in the console recipient property sheet.



PropertyValueDescription
Time RangeStart Time and End Time [hours of the day (defaults to 24 hours)]
Specify when during the day (start and stop times) this recipient receives alarms.
Days of the Week or Days of Weekcheck box
Specifies the days of the week to include.
Transitionsdrop-down list
Selects which alarm transitions to display in the console. Only those transitions selected display although the station saves all transitions in alarm history.

Options are: toOffnormal, toFault, toNormal, toAlert

Route Ackstrue or false
Enables (true) and disables (false) the routing of alarm acknowledgements to the recipient. The framework does not route trap (event notification) acknowledgements if you select false.
Default Time Rangedrop-down list of time optionsProvides a list of options for controlling how much information to display on the alarm console. If you select Time Range, the system prompts you for a beginning and ending time.