alarm-AlarmSourceInfo
This container slot is available on any network component, and each child device component. The slot’s properties populate the alarm record when the network or device does not respond to a monitor ping. This ping is configured at the network level.
Each parent and child device object has its own Alarm Source Info slot with identical (but independently maintained) properties.

Note: For how to format alarm source information on a report, click on the help icon to the right of the field.
| Property | Value | Description |
|---|---|---|
| Alarm Class | read-only used in Lists, console columns, or %alarmClass% on a report. | Defines alarm routing options
and priorities. Typical alarm classes include High, Medium and Low. An alarm class
of Low might send an email message, while an alarm
class of High might trigger a text message to the
department manager. |
| Source Name | text | Displays the name in an alarm
record that identifies the source of the alarm. |
| To Fault Text | text | Enters the text to display when
the component transitions to a Fault status. When applicable, text
entered for Fault Algorithm, High Limit
Text and/or Low Limit Text may override
this text. |
| Too Offnormal Text | text | Enters the text to display when
the component transitions to an Offnormal (alarm) state. When applicable,
text entered for Fault Algorithm, High
Limit Text and/or Low Limit Text may
override this text. |
| To Normal Text | text | Configures what displays
when the component transitions to a normal status. When applicable,
text entered for Fault Algorithm, High
Limit Text and/or Low Limit Text may
override this text. |
| Hyperlink Ord or Hyperlink | Ord, BQL Query or path | Associates an ORD, BLQ query
or path with an alarm state on the component. When an alarm is reported
in the console, the Hyperlink button activates. Clicking this button
links to the location you specify here. |
| Sound File | ord | Configures the path to a sound
file that plays when the current component is in an alarm state. Use
the folder icon to browse to the file. Click the arrow icon to the
right of the folder icon to test the path. |
| Alarm icon | text | Defines the path to a graphic file the system includes in the Timestamp column of the alarm table in the Console Recipient view. Use the folder icon to browse for the file. Use the right-arrow to test the location you entered. |
| Alarm Instructions | text | Advice that accompanies the alarm notification (Alarm Record window) that provides important information for the operator. Click the right-pointing arrow to view the instructions. |
| Meta Data [alarms] | text | Defines additional information
for the extension. |