Filters window

This window displays the properties you can use to include or exclude alarms from the alarm console. This filter action only affects which alarms display in the alarm console; it cannot be used to edit an alarm record or perform alarm maintenance. To access it, click Filter in the bottom of the Alarm Console Window or in the top right-hand corner. If you set the Filter on, The Filter button turns to red. To select multiple enums, use ctrl+click.

Note: If you are filtering on a field that uses a wildcard (Source, Alarm Class or User), make sure to put the percent character (%) at both ends of the text string, otherwise, the filter does not work.


PropertyValueDescription
Source State or sourceStateNormalHigh LimitThe status of the entity at the time the event, such as an alarm, occurred.
Ack StateAcked or Unacked
Indicates if the alarm has been acknowledged.
Ack Requiredtrue or false
Indicates if the alarm must be acknowledged (true) or not (false).
Source%alarmData.sourceName%Displays the path to the point that is generating the alarm.
Note: For how to format this information on a report, click on the help icon to the right of the field.
Alarm Classread-only used in Lists, console columns, or %alarmClass% on a report.
Defines alarm routing options and priorities. Typical alarm classes include High, Medium and Low. An alarm class of Low might send an email message, while an alarm class of High might trigger a text message to the department manager.
Priority (for the on-call contact)1–255 for each transition, default: 255; %priority% on a report
Specifies the order in which the OnCallService sends alarm notifications to the OnCallContact. Colors graphically identify alarm priority levels. You set up Priority levels using the alarm options window. The contact with the lowest number (highest priority) receives notification first. An alarm that is not acknowledged within the designated time is forwarded to the next contact in the list.
Note: Contacts may share the same Priority number. The OnCallService sends an identical notification to all contacts that have the same priority number
Normal Time or NormalTimedate and time
Displays the date and time (if applicable) that the alarm state returned to normal.
Ack Timehours:minutes:seconds
Displays the time that the alarm was acknowledged (if applicable).
User [provisioning]textThe station user that requested the job. This column displays unknown if job was triggered by a linked schedule.
Alarm Dataread-only
Presents a detailed list of alarm data, including this information: Status, toState, msgText, Count, fromState and Timezone.
Alarm Transitiontext
Shows the initial source state that generated the alarm. This value may not reflect the current state of the alarm source. Once the framework creates an Alarm Transition, it does not change for a single alarm record. For example, if the source state returned to normal after an offnormal status, this value remains at offnormal.
Last Updateread-onlyDisplays the time the system most recently updated the alarm.