This topic explains configuring the On-Call Schedule by
using the Alarm Class and On Call
Recepient in the Wiresheet. The On Call Service alarms are not handled automatically. You must determine and specify
which alarms should be sent to your On-Call Lists and configure them
to be routed. The alarms raised from the Alarm Class are handled by the On-call Lists. Based on the scheduling, the active
user receives a notification when an alarm is raised. You can also
verify the configured schedule, for a particular user, for a queried
time period.
- Open the OnCall palette, drag the OnCallRecipient to the Alarm Service folder.
- Switch to the Wire Sheet view of
the Alarm Service, use the relation link from
the Alarm Class to the On Call Recipient.

- Expand and double-click On Call List Schedule.
The
Scheduler view opens. This schedule
determines which OnCallLists is active and Inactive for the specified
time.

- Configure the schedule for the respective onCallList and
click Save.

Note: The scheduler view should not have any empty spaces. If
a space is empty, any alarms raised during that empty space not sent
to any OnCallList.
- To verify the schedule for the particular user, double-click
on the user.
The
On Call User Report View opens.
It shows the schedule for which user is on call.