Alarm Record window

This window shows additional detailed information about a specific point alarm.

Information



NameValueDescription
Timestamphours:minutes:seconds%timestamp% (on a report)
Reports the date and time the event occurred.
Uuidread-only
Displays the Unique Universal Identifier (UUID) the system uses to identify the alarm record.
Source State or sourceStateNormalHigh LimitThe status of the entity at the time the event, such as an alarm, occurred.
Ack StateAcked or Unacked
Indicates if the alarm has been acknowledged.
Ack Requiredtrue or false
Indicates if the alarm must be acknowledged (true) or not (false).
Source%alarmData.sourceName%Displays the path to the point that is generating the alarm.
Note: For how to format this information on a report, click on the help icon to the right of the field.
Alarm Classread-only used in Lists, console columns, or %alarmClass% on a report.
Defines alarm routing options and priorities. Typical alarm classes include High, Medium and Low. An alarm class of Low might send an email message, while an alarm class of High might trigger a text message to the department manager.
Priority [alarm]read-only
Reports the alarm ranking on a pre-defined importance scale. The lower the number, the higher the priority.
Normal Time or NormalTimedate and timeDisplays the date and time (if applicable) that the alarm state returned to normal.
Ack Timehours:minutes:seconds
Displays the time that the alarm was acknowledged (if applicable).
User [alarms]Drop-down listIdentifies the person that acknowledged the alarm. An unacknowledged alarm displays “unknown.”
Alarm Dataread-only
Presents a detailed list of alarm data, including this information: Status, toState, msgText, Count, fromState and Timezone.
Alarm Transitiontext
Shows the initial source state that generated the alarm. This value may not reflect the current state of the alarm source. Once the framework creates an Alarm Transition, it does not change for a single alarm record. For example, if the source state returned to normal after an offnormal status, this value remains at offnormal.
Last Updateread-onlyDisplays the time the system most recently updated the alarm.

Buttons

ButtonValueDescription
left and right arrowsbuttonsIf multiple records exist for an alarm, which can happen if repeated alarm transitions occur unacknowledged, arrow buttons may be enabled at the bottom corners of this dialog box:
  • Go to previous alarm record (back in time)

  • Go to next alarm record (forward in time)

AcknowledgebuttonRecognizes each selected alarm.
HyperlinkbuttonChanges the current view to the hyperlinked target associated with the selected alarm. If no hyperlink is associated with the alarm, the Hyperlink button is not available.
NotesbuttonDisplays the Notes dialog box for the purpose of adding a note to the selected alarm or alarms.