AlarmClassMapper
Alarm class mapping provides a way to assign one or more alarm classes to a common set of alarm-handling parameters. You access this mapper from the alarm console by clicking or by clicking the chevron next to this property on the Alarm Console property sheet.
Alarm Class Mapper window
One benefit of this type of mapping is that you can import alarms from a variety of alarm classes and have them display, link, or sound in a common manner. You do this by creating alarm class definitions and then associating (mapping) existing alarm classes to these definitions.

The window has two panes:
Upper pane: Alarm Class Definitions allows you to create, delete, or edit alarm mapper definitions before assigning them to existing classes.
Lower pane: Alarm Class Definition Mapping assigns any existing alarm classes to the selected definition.
Buttons
| Button | Value | Description |
|---|---|---|
| New | button | Opens the window used to create the entity you are working on |
| Edit | button | Opens the Edit dialog box. Use this dialog box to edit an entity. Which entity to edit depends on the context within the system. |
| Delete | button | Removes the selected record from the database. |
| Add Mapping | button | Opens the Map Alarm Class window, which is where you associate an alarm class with a definition. |