Acknowledging an alarm verifies human awareness that a
potentially detrimental event has occurred or a condition exists with
a device that is outside its normal range of operation. You cannot
remove an alarm until you acknowledge it and until the alarm source
returns to a normal state (no longer in alarm).This procedure acknowledges
alarms from the alarm console.
A ConsoleRecipient exists in the station.
- To display the AX Alarm Console, right–click
the ConsoleRecipient node in Nav tree and click .
The
AX Alarm Console opens.

Each record that appears in the alarm console table represents
one alarm source and one or more alarms from that source.
- To silence an alarm, select it and click the Silence button at the bottom of the view.
- To sort the alarms in order of any column, click the column
title (once for ascending, twice for descending).
- To view all current alarms from a particular point, double-click
point’s row in the table.
This opens the Open Alarm Sources view.
- To use sound options, click the sound icon in the toolbar
of the AX Alarm Console window.
- Select one or more alarms to acknowledge. You may select
multiple alarms using the Shift or Ctrl keys.
- To view details about the selected alarm, double-click
the alarm row in the table or select the alarm and click the Hyperlink button at the bottom of the AX Alarm
Console view.
- To acknowledge one or more alarms, do one of the following:
- To acknowledge the latest (most recent) alarm(s), right-click
the selected alarm(s) and click Alarm Acknowledge Most
Recent or click from the menu.
- To acknowledge all alarms that are reported from a single
source, click or click the Acknowledge All button at the bottom of the console.
The system acknowledges the latest or all alarms from
each selected alarm source.