In addition to common Nrio Proxy Ext properties, the following additional properties are available in the NrioCounterInputProxyExt:
Specifies whether count total (Count) or count rate (Rate) is at the Out slot, as a status numeric. Default is Count.
(read only) Total number of pulses counted since the Proxy Ext was last set or reset. Data type is Baja Long.
(read only) Calculated rate, based upon Rate Calc configuration. Data type is Baja Double.
Selectable to one of three types provided in the Nrio module:
Contains from one to three properties used in rate calculation, according to the selected rate calc type (see “About Nrio rate calculation”):
Default is value is 1. Appropriate value depends on the item quantity/pulse and desired rate units. Two examples are provided:
Power Meter
Each meter pulse indicates 0.15 kWh, and desired rate units is kW.
Scale = 3600 (sec/hr) * 0.15 kWh/pulse = 54
Liquid Flow Meter
Each meter pulse indicates 0.375 liters, and desired rate units is liters/minute (L/min).
Scale = 60 (sec/min) * 0.375 liters/pulse = 22.5
(not available if TriggerRateType) Default is value is 1 minute.
(available only if SlidingWindowRateType) Default is value is 6.
(read only) Reflects timestamp of last rate calculation.