500 Ohm Shunt produces a “secondary” selection for conversion type, with all conversion types shown again. However, only two secondary
Conversion types are valid for 500 Ohm Shunt:
In the Scale and Offset fields for this Linear conversion, you enter whatever calculated values are needed to display in the appropriate units of measurement for that sensor. The following image shows an example configuration of such a point.

For background on this example configuration, see “Scale and offset calculation example 2”.
In this case, you must enter (or import) a custom “source and result” .xml curve file, where the source (signal) values are between 0 to 10 (volts, where you multiply each mA value * 500), and the corresponding results are the measured values, in whatever units.