A VoltageOutputWritable is a NumericWritable with NrioVoltageOutputProxyExt. It represents a 0-to-10Vdc analog output (AO). All standard NumericWritable features apply, including right-click actions and priority input scheme.

The point’s Proxy Ext contains common Nrio Proxy Ext properties. Among those properties, note that the read-only “Device Facets” is set to units Volts (V). For operation in units other than volts, see “Scale and offset calculation (linear)”.
In addition to the common Nrio Proxy Ext properties, the following additional properties are also available under a Hardware Override container slot.
(read only, transient) Either false or true, as to whether the hardware override switch is active. Uses Baja data type Boolean.
Either false or true (default). Enables a hardware override to mark the parent point in fault (while overridden is true).
Either false (default) or true. Enables a hardware override to mark the parent point in alarm (while overridden is true).
If you configure both Fault Enable and Alarm Enable true, a fault alarm is generated upon an active hardware override.
The alarm class to use for a hardware override-generated alarm or fault.