VoltageOutputWritable

A VoltageOutputWritable is a NumericWritable with NrioVoltageOutputProxyExt. It represents a 0-to-10Vdc analog output (AO). All standard NumericWritable features apply, including right-click actions and priority input scheme.

Figure 32.   Nrio Voltage Output Writable
Image

The point’s Proxy Ext contains common Nrio Proxy Ext properties. Among those properties, note that the read-only “Device Facets” is set to units Volts (V). For operation in units other than volts, see “Scale and offset calculation (linear)”.

In addition to the common Nrio Proxy Ext properties, the following additional properties are also available under a Hardware Override container slot.

 
NOTE: The following four Hardware Override properties were intended for a I/O hardware module that was never supported. Therefore, they are not functional and can be safely ignored.
 

  • Overridden

    (read only, transient) Either false or true, as to whether the hardware override switch is active. Uses Baja data type Boolean.

  • Fault Enable

    Either false or true (default). Enables a hardware override to mark the parent point in fault (while overridden is true).

  • Alarm Enable

    Either false (default) or true. Enables a hardware override to mark the parent point in alarm (while overridden is true).

    If you configure both Fault Enable and Alarm Enable true, a fault alarm is generated upon an active hardware override.

  • Alarm Class

    The alarm class to use for a hardware override-generated alarm or fault.