A ResistiveInputPoint is a NumericPoint with NrioResistiveInputProxyExt. It configures a UI to read a resistance from 0 to
100,000 ohms. Default configuration provides ohms. If other units are needed, select conversion type of either Linear (for
linear response) or Generic Tabular, if non-linear.
NOTE: Universal inputs (UIs) are optimized for resistive temperature sensors in 10K ohm range. Any temperature sensor far outside
this range, for example a 100 ohm or 1K ohm type, will have poor resolution—and thus be unusable! In this case, install a
compatible transmitter that provides a linear 0-to-10V or 4-to-20mA signal, and use a VoltageInputPoint instead.
The ResistiveInputPoint is pre-configured with a linearCalibration extension, to allow for offset correction.
Figure 26. Nrio Resistive Input Point
The ResistiveInputPoint’s Proxy Ext contains only common Nrio Proxy Ext properties. Among these, note that the read-only “Device
Facets” property is preset to ohms.