Editing the Join Profile

In the Join Profile Manager, select the JoinProfile for the Supervisor, and then click the Edit button for a popup dialog, as shown in Figure 20.

NoteAlternatively, you can simply double-click the JoinProfile for its property sheet, which contains all the properties shown below, plus a “Status” property and a “Station Info” container. See StationInfo for additional details.

Figure 20. Edit dialog for JoinProfile of Supervisor

Edit dialog for JoinProfile of Supervisor

The following fields are in this dialog:

In AX-3.7u1 and later, when you are pre-engineering a JACE for eventual Join to a Supervisor, (where you want to do as much engineering as possible in the JACE station or if you do not have access to the Supervisor station), there are properties that you need to configure. Specifically, the default subordinate user credentials in the JoinProfile must be configured in order to avoid authentication errors during the Join process.

Adding default subordinate user credentials to a pre-engineered NiagaraStation

  1. Under the subordinate JACE station’s NiagaraNetwork, double-click the SubordinateExportTagNetworkExt to open the Join Profile Manager view.

  2. Select the JoinProfile for the Supervisor, and then click the Edit button for a popup dialog.

  3. Enter a Default Subordinate User name (something that the Supervisor will recognize).

    NoteTypically, the Default Subordinate User account should be a user that was created especially for station-to-station access, typically with admin write privileges, and not otherwise used for normal (login) access of the station.

  4. Enter the Default Subordinate User Password for that user.

  5. Click OK after making changes, as shown here:

    Figure 21. Adding local station user credentials for Supervisor to connect back to this station

    Adding local station user credentials for Supervisor to connect back to this station

    After adding these properties you can issue a Join from the JACE station. The new NiagaraStation (representing that JACE) is added, where it has all the pre-engineered PxViews, points, etc from its export tags.

    If an incorrect user name or password (or no password) is used, the Join will fail with authentication errors. Refer to the Job Log to confirm, as shown here:

    Figure 22. Job Log shows Supervisor Authentication Failed error message