When I start a station the BACnet/Ethernet Port goes into fault with the message, “Verify WinPcap 4.1.x is installed.”
WinPcap must be manually installed to use BACnet/Ethernet on supported
I have connected all network devices as described in the documentation, but
Failure to discover may be due to:
Use bacnetUtil to diagnose the above problems.
How can I diagnose intermittent MS/TP network problems
The BTokens component may be the most useful MS/TP troubleshooting tool. This component provides visibility into the health of an MS/TP network at a new level. Previously this type of information could only be gathered by observing and interpreting the blink pattern of the device’s serial activity LEDs. Knowing the bus is healthy at the token passing level may help shift the focus of an investigation to a remotely solvable configuration problem that does not require dispatching a technician to the site to investigate.
Initial offsite diagnosis of intermittent problems can be performed using the BTokens component, standard
How can I improve performance of older devices
Device overrides can be a useful tool for managing performance limitations in some devices. For example, older devices in
the field may claim support for features like “readPropertyMultiple” (answering multiple questions per request), but do not
do a great job of answering large multiple question requests in a timely manner. Those older devices may be able to more quickly
respond to 30 separate requests containing only one question, than one request containing 30 questions. Adding an rpmOverride to the device may improve overall performance of communication with the device by instructing