New (and Edit) local variable window

This window adds discovered points to the station database and configures them with direction (input or output), SNVT type, and a name for each variable.
Figure 72.   New variable window
Image

To access this window, double-click the LonNetwork node in the Nav tree, double-click the Local Lon Device followed select a network variable and click the Edit button.

Property Value Description
Name text Provides a name for the nvi, nvo, or nci variable. If part of a data structure, it provides a trailing _elementName, which ensures a unique point name. For example, nciTempSetPts_occupiedCool

This value does not affect the Lonworks node. You may change it as needed.

Direction drop-down list (for a new variable defaults to Input and for a existing variable, this value is read-only)
Configures or indicates the direction of travel of the message: to the station (Input) or from the station Output.
SnvtType drop-down list Selects the Standard Network Variable Type (Snvt).

If you are using an .lnml file, leave this property at its default SNVT Xxx value.

SelfDoc string of text (defaults to: &3.0@;Niagara Server Node) This property requires External Config to be set to true
Defines a text string for the host node’s self documentation up to 1024 bytes. A single asterisk (*) omits self documentation.
 NOTE: When using self documentation, always retain the leading header portion (&3.0@) along with an additional zero (0), plus other characters. 
Lnml File file name Defines the file for a device that implements the UNVT (User–defined Network Variable Type) needed.

This file contains device, point and variable information. A Quik Learn automatically uses it to create Lon devices. The file extension is .lnml

Type for variables: drop-down list Selects a number for network variable type.

This value works in conjunction with the Lnml File property, where, once you specify an .lnml file, Type provides a list of UNVTs from which you can choose this nv.